Overview
The intelligent electromagnetic flowmeter consists of two parts: a sensor and a converter. It is based on Faraday’s law of electromagnetic induction and is used to measure the volume flow of conductive liquids with a conductivity greater than 5 μS / cm.
In addition to measuring the volumetric flow of general conductive liquids, it can also be used to measure the volumetric flow of highly corrosive liquids such as strong acids and alkalis, and uniform liquid-solid two-phase suspension liquids such as mud, pulp, and pulp. After setting the density, the mass flow of the conductive liquid can be measured.
Technical Specification
Nominal Diameter | DN3 to DN1200 |
Electrode Material | 316L, Hb, Hc, Ti, Tan, Pt |
Lining Material | Neoprene, Polyurethane, PTFE, PFA, F46 |
Dielectric Conductivity | ≥5μS/cm, (softened water ≥ 20μS/cm) |
Accuracy Level | ±0.5%R~±1.0%R |
Flow Range | 0.3m/s~12m/s |
Ambient Temperature | -20℃~+60℃ |
Medium Temperature | A:≤80℃;B:≤120℃;C:≤180℃ (split PTFE lining) |
Nominal Pressure | 0.6MPa~4.0MPa (based on the meter size or special order) |
Protection Level | IP65, IP67, IP68(remote-type) |
Output Signal | 4~20mA,frequency/pulse, alarm output |
Communication | RS485, RS232, MODBUS485, HART, PROFIBUSDP |
Power Supply | 220VAC,24VDC |
Installation Type | Compact/Remote |
Flange Standard | GB, ANSI, JIS, DIN |
Shell& Flange Material | Stainless steel, carbon steel, etc. |